Configure noise rating limits and room attenuation values to evaluate acoustic performance against specific dB requirements for defined spaces.
Before you start, ensure that rooms are defined in your model using space management tools and that all air terminals are placed within these room boundaries.
- Access the Drawing settings within your platform and go to the section.
-
Configure the following global parameters for the acoustic analysis:
- Noise limit in room [dB]: Select the target noise rating (NR) level (for example, NR 35) from the list. The system uses this value to determine the specific dB limit for each octave band.
- Noise attenuation of room [dB]: Define the sound damping value for a typical room (the default is 10 dB). This value is subtracted from the terminal's noise level before calculating the total room noise.
-
Execute the ventilation calculation and ensure that the Calculate noise option is enabled.
The calculation report now includes the room noise results and specifies any required silencing needed to meet the defined NR limit.