Configure default ventilation calculation parameters

Modified: 6 May 2026 Stabicad
Stabicad
Stabicad

Configure project-wide defaults for duct types, air leakage ratios, and physical air properties within StabiBASE.

Setting the default parameters ensures that whenever a new duct is drawn or a calculation is performed, Stabicad applies the correct regional or project-specific technical constraints automatically.

  1. Go to StabiBASE > Manage > Drawing settings.
  2. Go to the Ventilation > Calculation section.
  3. Configure the following key parameters as required for your project:
    • Duct Type Defaults: Define the design velocity, maximum velocity, and maximum pressure loss per meter for the main, connection, and shaft duct types.
    • Air Leakage (By factor): Set the system leakage ratio (for example, 5%).
    • Air Leakage (By standard): Define the leak factor of the custom class (for example, 0.00003).
    • General: Set the physical properties for air density (typically 1.2 kg/m³) and kinematic viscosity (typically 15.06e-6 m²/s).
    • Noise: Configure the acoustic settings as described in the specialized noise calculation tasks.
The calculation parameters are now configured.