Provides the mathematical formulas and rules used to determine peak flow rates and individual device discharge units in waste water systems.
Peak flow calculation (Qww)
| Calculation | Description | Formula |
|---|---|---|
| Peak flowrate | Calculates the waste water flowrate (Qww) based on the building's usage and the sum of connected discharge units. |
Qww = K · √ΣDU Where:
|
| Individual device rule | Ensures that the final pipe flow is sufficient for the largest connected appliance. |
Qpipe = max(Qww, max(DUi)) Where:
|
Frequency factor (K)
The frequency factor (K) is determined by the specific usage of the building:
- Intermittent: 0.5
- Frequent: 0.7
- Congested: 1.0
Sanitary equipment mapping
Each calculation standard defines mandatory base flows for appliances. If a manually entered value is lower than the minimum required by the selected standard, the system issues a warning but allows the calculation to proceed.