General ventilation formulas

Modified: 6 May 2026 Stabicad
Stabicad
Stabicad

Foundational formulas and logic for determining air flow, velocity, and balancing requirements in duct systems.

Flow and velocity formulas

Calculation Description Formula
Flow calculation The flow in any duct segment determined by the sum of all downstream air terminal flows connected to it, plus any calculated air leakage.
Velocity calculation Determines air velocity based on flow rate and cross-sectional area.

v = Q / A

Where:

  • v: Velocity (m/s)
  • Q: Flow (m³/s)
  • A: Cross-sectional area (m²)

Duct geometry and air properties

Calculation Description Formula
Hydraulic diameter Used for rectangular ducts to calculate equivalent round diameters for pressure loss calculations.

dh = 4A / P = 2ab / (a + b)

Where:

  • dh: Hydraulic diameter (m)
  • A: Cross-sectional area (m²)
  • P: Perimeter (m)
  • a, b: Height and width of the duct (m)
Reynolds number The ratio of inertial forces to viscous forces within the air flow.

Re = (c · d) / ν

Where:

  • c: Velocity (m/s)
  • d: Hydraulic diameter (m)
  • ν: Kinematic viscosity (m²/s, sourced from StabiBASE)

Pressure balancing logic

Calculation Description Formula
System pressure The total pressure loss of the path with the highest resistance (the critical path). The total pressure loss of the critical path becomes the required system pressure. The control pressure for this path is 0.
Control pressure The required pressure dissipation for non-critical paths to achieve design flow.

Pcontrol = Psystem - Ppath

Where:

  • Pcontrol: Value to be absorbed by a balancing damper
  • Psystem: Pressure of critical path
  • Ppath: Pressure of the current path
Submit