Understand the available calculation engines, the mandatory system requirements for modeling heating and cooling networks, element types and properties, supported scenarios, and standard-specific workflows.
Calculation engines: Local and cloud
Stabicad provides two distinct calculation engines for heating and cooling systems:
| Engine type | Description |
|---|---|
| Local calculation |
|
| Cloud calculation (Revit only) |
|
System requirements
To perform a successful heating and cooling calculation, the Revit model must meet specific technical criteria. Ensure the following requirements are satisfied before launching the calculation engine:
| Criterion | Requirement |
|---|---|
| Two-pipe topology | The system must consist of a supply and return path. Loops and one-pipe systems are not currently supported. |
| Connected network | Systems must be fully connected with a defined provider, such as a boiler or chiller, and consumers. Open-end calculations are supported in newer cloud versions. |
| System types | Pipes must be assigned to recognized Revit system types, specifically Hydronic Supply and Hydronic Return. |
Supported scenarios and limitations
The following matrix defines the compatibility of various project scenarios with the local and cloud calculation engines:
| Scenario | Cloud | Local |
|---|---|---|
| Generic heating and cooling consumer - rigid piping | Supported | Supported |
| Generic heating and cooling consumers - flexible and bendable piping | Control calculation only | Supported |
| Radiators (panel, design, column, convector) | Supported | Supported |
| Air heaters, air curtains, batteries | Supported | Supported |
| Boiler / chiller | Supported | Supported |
| Manifold (distributor or as consumer) | Supported | Supported |
| Fan coil unit (FCU) | Supported | Supported |
| Heat interface unit (HIU) | Supported | Not supported |
| VAV boxes, induction diffusers | Not supported | Supported |
| 6-way valves | Not supported | Supported |
| 3-way valves | Not supported | Not supported |
| Saddles, welds, and connection blocks | Supported | Supported |
| Resistances with 1 connector | Supported | Supported |
Legend
- Supported: Full calculation and dimensioning
- Control calculation only: The element is recognized for control calculations but not fully dimensioned
- Not supported: The calculation will fail or ignore these elements
Element types and detailed properties
Providers (heat and cold sources)
Providers define the global system parameters for the calculation network.
| Provider type | Detailed properties |
|---|---|
| Boiler | Input properties include supply and return temperatures, as well as specific Zeta or pressure loss values for the equipment. |
| Chiller | Includes settings for glycol type and percentage, which significantly affect fluid density and kinematic viscosity. |
| Combi-boiler | Shares properties between the heating and tap water modules, though Zeta and pressure loss values are tracked separately for each discipline. |
Consumers (emitters)
Consumers represent the terminal devices or equipment that utilize the heating or cooling energy provided by the system.
| Consumer type | Detailed properties |
|---|---|
| Radiators | Properties include design power (W), flow (l/s), and Delta T. Users can select "Lock Dimensions" to prevent the engine from resizing the radiator connectors. |
| Heat interface units (HIU) | Specific to CIBSE CP1 calculations, these represent the demand of an entire apartment. They are available only in Revit and are placed via the HIU button in the ribbon. Unique parameters include undiversified DHW and space heating demand, and the amount of dwellings served. |
| Generic consumers | Generic blocks used to represent one or more heating consumers where users define the calculation base as either power or flow. |
| Specific consumers | Includes fan coil units, air heaters, or batteries. These can be placed as generic families or manufacturer-specific elements. |
| Manifolds | Can be utilized as a consumer to represent the total power requirements of floor heating systems. |
Standard-specific heating and cooling workflows
CIBSE CP1 (UK district heating)
When the "Diversify loads according to CP1" option is enabled in the cloud calculation, the engine applies specific diversification logic for secondary networks:
- DHW diversification: The engine calculates a diversified flow rate (qd) for each pipe section using the sum of downstream HIU demands and a probability factor (theta).
- Space heating diversification: The total heating flow is reduced as the number of dwellings (n) increases using the formula: 0.62 + (0.38 / n).
- Combined flow: The final pipe size is determined by the sum of the diversified domestic hot water and space heating flows.
ISSO 18 (Netherlands/standard Zeta logic)
Stabicad implements high-fidelity Zeta calculations for fittings based on the ISSO 18 standard:
- Bends: The engine corrects the basic Zeta (ζ0) value by applying a Reynolds correction (CRe) and a roughness correction (Cw).
- Tees: The calculation implements complex split and merge flow logic based on the velocity in the main branch versus the branch branch.
- Global configuration: Users can define tees as "sharp" or "rounded" globally within the drawing settings in StabiBASE.