Heating and cooling pressure loss calculation

Modified: 8 May 2026 Stabicad
Stabicad
Stabicad

Provides technical data and formulas for determining total pressure loss, including pipe friction, fitting resistances, and static pressure effects.

Total pressure loss

The total pressure loss in the system is determined by summing the losses from pipes, fittings, equipment, and static head:

ΔPtotal = ΔPpipe + ΔPfitting + ΔPdevice + ΔPstatic

Loss along pipes

Pipe pressure loss is calculated using the Darcy-Weisbach equation:

Δppipe = λ · (L / D) · (1/2)ρ · v²

The friction factor (λ) is determined based on the flow regime:

Flow regime Formula / Method
Laminar flow (Re < 2000) λ = 64 / Re
Turbulent flow (Re > 3000)
  • CIBSE/UK (Haaland): 1 / √λ = -1.8 · log[(6.9 / Re) + ((k/D) / 3.71)1.11]
  • ISSO/NL (Colebrook-White): 1 / √λ = -2 · log((ε / (3.72 · D)) + (2.51 / (Re · √λ)))

Loss on fittings and equipment

For fittings and equipment, pressure loss is determined by the following formula:

ΔP = ζ · (1/2)ρ · v²

Method Description
ISSO 18 standard Calculates ζ based on geometric characteristics such as angles, radii, and area ratios
Factor method Calculates fitting loss as ΔPfitting = ΔPpipe · factor. The default factor is typically 0.2 or 1.2 depending on localization

Static pressure and thermosiphon

Static pressure loss is caused by gravity and differences in elevation:

ΔPstatic = ρ · g · ΔH

Thermosiphon effect: Stabicad calculates different densities for supply and return water, which incorporates the thermosiphon effect into the static pressure results.