Skip to main content

Import thermal loads

Modified: 8 May 2026 Stabicad
Stabicad
Stabicad

Integrate external thermal demand calculations from Vabi Elements or IESVE into the hydraulic sizing process to ensure system designs meet actual building loads.

Integrating thermal loads from specialized building physics software ensures that hydraulic networks are sized to satisfy the actual heating and cooling requirements of a building. This process involves exporting model geometry via IFC to external simulation tools and re-importing the resulting power requirements into Revit spaces via Excel files. Once imported, you can verify that the installed equipment capacity matches the required load before performing the final hydraulic calculation.

Import thermal loads from Vabi (NL)

The Vabi calculation workflow uses Vabi Elements to handle complex building physics, ensuring the hydraulic system is sized according to the actual thermal loads of the building.

  1. Prepare the model for export.

    Ensure the Revit model, whether an architectural model or an MEP model with linked architecture, has properly defined spaces.

  2. Export the model to IFC.

    The IFC file must contain the geometry and space definitions required for thermal simulation.

  3. Perform the Vabi simulation.

    Load the IFC file into Vabi Elements and perform the required thermal heat loss and cooling load calculations.

  4. Export the calculation results to Excel.

    The Excel file must include the calculated power requirements, such as transmission and cooling loads, per space.

  5. Import the Vabi results into Stabicad.
    1. In Revit, click the Import from Excel (Vabi results) button.
    2. Stabicad maps the data to the corresponding spaces and populates the Transmission [W] or Cooling Load [W] parameters.
  6. Verify consumer capacity.

    Use the default schedule provided by Stabicad to compare the Required Load imported from Vabi against the Installed Capacity of the placed consumers. This ensures each space has sufficient power before proceeding.

  7. Run the hydraulic calculation.

    Once the loads are satisfied, run a local or cloud calculation to size the pipes and determine pressure drops.

Import thermal loads from IESVE (UK)

The IESVE workflow is specifically designed for the UK market, allowing engineers to import calculated heating and cooling loads directly into Stabicad. This ensures the hydraulic design matches the simulated building performance.

  1. Prepare the model.

    Ensure that the Revit model contains defined spaces or rooms.

  2. Export the model to IFC.

    Use the IFC export to transfer the model geometry and space or room data to IESVE.

  3. Perform the IESVE simulation.

    Import the IFC file into IESVE and perform the necessary heating and cooling load calculations.

  4. Export the results to Excel.

    Export the IESVE result sheet to an Excel file. Stabicad uses the space or room name and number combination to match the Excel data to Revit elements.

  5. Import the IESVE results into Stabicad.
    1. In the palette center (second row, third column), click the Import IESVE results button and select the valid output file.
    2. Stabicad maps the results to specific parameters, such as IESVE Calculated Heating Load and IESVE Calculated Cooling Load.
  6. Verify design coverage using the IESVE schedule.

    Use the dedicated IESVE schedule provided in the template to track the IESVE Calculated Load against the Installed Capacity of radiators or fan coil units. This provides a visual check to ensure the design meets the simulated requirements.

  7. Execute the hydraulic calculation.

    Finalize the design by running the Stabicad calculation to size the pipework based on the imported IESVE loads.

Submit