NTR 3216 sizing formulas (NL)

Modified: 7 May 2026 Stabicad
Stabicad
Stabicad

Provides the specific hydraulic formulas, lookup tables, and exceptions for sizing stack, branch, and ventilation pipes according to the Dutch NTR 3216 standard.

Stack pipe dimensioning

Stack pipes are main vertical conduits that must maintain a consistent diameter throughout their entire length based on the flow calculated at the bottom (end) of the stack.

Table 1. Calculation by length
Calculation Description Formula / Method
Length ≤ 50m Standard calculation for internal diameter based on flow and capacity factors.

d = √(Qa / (λ · s))

Where:

  • d: Inner diameter of the pipe (m)
  • Qa: Calculated flow (l/s)
  • λ: Constant value of 400 (m/s)
  • s: Drain capacity factor (1.4 for length ≤ 10m; 1.0 for 10m to 50m or parallel ventilation)
Length > 50m Calculation for high-rise stacks. The diameter must be read from Table 5.09 (Maximum discharge flow rates in high-rise stacks).

The "one-size reduction" exception

If the stack pipe length (excluding the ventilation pipe) is ≤20m, the top 10m may be dimensioned one size smaller than the bottom section if the flow allows it. This exception does not apply if:

  • The ventilation pipe itself is longer than 10m.
  • The system is a direct/indirect parallel ventilation system.

The Chézy formula

Branch and drain pipes are dimensioned per section using the Chézy coefficient, typically involving an initial estimation followed by iteration.

Calculation Description Formula
Chézy coefficient (C) Determines the coefficient used for initial diameter estimation and iteration.

C = γ · log(3 · d / k')

Where:

  • γ: Constant value of 18
  • d: Estimated inner diameter (m)
  • k': Wall roughness constant of 0.001
Design diameter (d) Final diameter calculation for branch and drain pipes.

d = (Qa / (315 · f · C · √I))0.4

Where:

  • f: Bend factor (1 or 0.85)
  • I: Slope of the pipe (m/m)

Determining the bend factor (f)

The factor f is set to 0.85 if the total horizontal change of direction exceeds limits defined by slope. If a branch vent is connected, f is always 1.

Slope range (mm/m) Max total change of direction (°)
20 - 1320
13 - 1045
10 - 767
7 - 5.590
5.5 - 7112

Connection pipe definition

The connection pipe connects a single appliance to the rest of the system. For simplicity in Stabicad, the entire connection pipe is dimensioned based on the requirements of the horizontal "connecting pipe" II section.

Sizing

Calculation Description Formula / Rule
Standard appliances Determination of nominal diameters for standard sanitary components. Nominal diameters are pulled from a mapping table (e.g., Wash basin = 44mm, Toilet ≥ 7L = 100mm).
Custom flows Sizing logic used when the user manually alters default flow rates.

A generic lookup table is used:

  • 0.01 - 0.50 l/s: 44mm
  • 1.76 - 2.50 l/s: 100mm
Length rule Constraint applied based on the developed length of the connection pipe. If a connection pipe is longer than 3.5m, it must be dimensioned according to Branch/Drain pipe rules.

Ventilation pipe dimensioning

Requirement type Rule description
Standard rule Ventilation pipes should generally have the same diameter as the pipe they are connected to.
System minimum Every system must contain at least one ventilation pipe with a diameter of at least 69mm connected to the open air.

Size reduction exception

The ventilation pipe can be one size smaller than the stack pipe if all of the following conditions are met:

Condition Requirement
Stack length The stack pipe length must be less than or equal to 20m.
Combined length The combined length of the vent and the reduced stack section must be less than or equal to 10m.
Geometric limits The vent pipe must contain no more than four 90° bends or six 45° bends.