Perform a full system calculation to determine duct sizes, pressure losses, air leakage, and noise levels based on regional standards.
Before you start:
- Ensure the ventilation system is fully connected (ducts, fittings, and air terminals).
- Ensure all air terminals have a defined flow rate (for example, m³/h).
- Ensure the system has exactly one open end (typically the connection point for the Air Handling Unit).
- For DTU 68.3 calculations, define the minimum (Qmf) and maximum (QMf) flow rates on each terminal.
- For room noise calculations, ensure rooms are defined and noise settings are configured.
-
In , select the calculation standard:
- CIBSE GUIDE C (2007) + DW144 (2016): For UK-based projects.
- ISSO 17 (2010): For Dutch-based projects.
- DTU 68.3 (1995): For French-based projects.
-
Start the ventilation calculation feature and select the system in your model.
-
In the calculation dialog, configure the primary options:
- Recalculate existing diameters: Enable this to allow the software to resize ducts based on velocity and pressure constraints.
- Calculate noise: Enable this to perform acoustic analysis according to ISSO 24.
- Calculate air leakage: Enable this account for losses through joints.
- Appliquer Foisonnement: (DTU 68.3 only) Enable this to apply French simultaneity factors.
-
Select the Calculate fitting loss by method:
- Default standard: Uses detailed $\zeta$ (zeta) factor logic from ISSO 17 for high accuracy
- Fitting pressure loss factor: Uses a simplified percentage of the total duct pressure loss as defined in StabiBASE
-
If air leakage is enabled, click Air leakage properties and select a method:
- By factor: Adds a flat percentage (default 5%) to every duct flow.
- By standard: Uses ISSO 17 / DW144 formulas based on the selected airtightness class (A, B, C, D, or custom).
-
Click OK to run the calculation.
The system is updated with the following results:
- Ducts are resized if the recalculation option was selected.
- The critical path (highest pressure loss) is identified to set the system pressure.
- A control pressure ($P_{control} = P_{system} - P_{path}$) is calculated for all non-critical paths, indicating the pressure to be absorbed by balancing dampers.
- Detailed data is available in the Interactive Calculation overview or the generated report.