Perform a ventilation calculation

Modified: 26 Jun 2026 Stabicad
Stabicad
Stabicad

Perform a full system calculation to determine duct sizes, pressure losses, air leakage, and noise levels based on regional standards.

Before you start:

  • Ensure the ventilation system is fully connected (ducts, fittings, and air terminals).
  • Ensure all air terminals have a defined flow rate (for example, m³/h).
  • Ensure the system has exactly one open end (typically the connection point for the Air Handling Unit).
  • For DTU 68.3 calculations, define the minimum (Qmf) and maximum (QMf) flow rates on each terminal.
  • For room noise calculations, ensure rooms are defined and noise settings are configured.
  1. In StabiBASE > Ventilation > Calculation, select the calculation standard:
    • CIBSE GUIDE C (2007) + DW144 (2016): For UK-based projects.
    • ISSO 17 (2010): For Dutch-based projects.
    • DTU 68.3 (1995): For French-based projects.
  2. Start the ventilation calculation feature and select the system in your model.
  3. In the calculation dialog, configure the primary options:
    • Recalculate existing diameters: Enable this to allow the software to resize ducts based on velocity and pressure constraints.
    • Calculate noise: Enable this to perform acoustic analysis according to ISSO 24.
    • Calculate air leakage: Enable this account for losses through joints.
    • Appliquer Foisonnement: (DTU 68.3 only) Enable this to apply French simultaneity factors.
  4. Select the Calculate fitting loss by method:
    • Default standard: Uses detailed $\zeta$ (zeta) factor logic from ISSO 17 for high accuracy
    • Fitting pressure loss factor: Uses a simplified percentage of the total duct pressure loss as defined in StabiBASE
  5. If air leakage is enabled, click Air leakage properties and select a method:
    • By factor: Adds a flat percentage (default 5%) to every duct flow.
    • By standard: Uses ISSO 17 / DW144 formulas based on the selected airtightness class (A, B, C, D, or custom).
  6. Click OK to run the calculation.

The system is updated with the following results:

  • Ducts are resized if the recalculation option was selected.
  • The critical path (highest pressure loss) is identified to set the system pressure.
  • A control pressure ($P_{control} = P_{system} - P_{path}$) is calculated for all non-critical paths, indicating the pressure to be absorbed by balancing dampers.
  • Detailed data is available in the Interactive Calculation overview or the generated report.