Learn how to configure, execute, and verify waste water calculations to automatically size pipes and determine hydraulic flows based on international standards.
Waste water calculations allow you to perform hydraulic sizing for gravity-based systems by determining peak flows and identifying pipe roles. By connecting sanitary equipment to a defined endpoint and applying standard-specific rules, you can automate the dimensioning of your network to ensure it meets technical requirements for slope and capacity.
Set up waste water calculation
- Go to and select the applicable norm.
- Ensure exactly one waste water endpoint is placed at the discharge point of the connected network.
- Place appliances (toilets, sinks) and assign manufacturer codes if required (locking connector dimensions).
- In the endpoint properties, select Use of waste water (for example, frequent, congested) to set the frequency factor (K).
Run waste water calculation
Manually specify waste water pipe types
If the automatic calculation misidentifies the functional role of a pipe, you can manually override the classification.
- Select the pipe segment you want to change.
- Open the calculation properties for the selected segment.
- Set Pipe type definition method as User defined.
- Select the correct pipe type from the list (for example, drain or branch).
- Click OK.
Visualize pipe roles
Use the visualization tool to verify that the calculation has correctly identified the functional roles of all pipes in your network.
Troubleshoot a waste water calculation
Common error messages
| Error message | Description and solution |
|---|---|
| No starting point found | This message appears if Stabicad cannot identify the system exit. Ensure that a waste water endpoint symbol is correctly placed in the model and properly connected to the pipe network. |
| Flow might be too much | This message appears if the calculated flow rate for a specific segment exceeds the maximum value allowed in the standard sizing tables of the selected standard. |
Unsupported calculations and systems
Note the following limitations for waste water calculations in Stabicad:
- Rainwater and roof drainage calculations are not supported.
- System III is not supported for calculations using EN 12056 or BS EN 12056 standards.