Provides the technical constraints and iterative methodology used by the calculation engine to determine pipe diameters based on velocity and pressure loss limits.
Sizing methodology
The calculation engine utilizes the Gradual Velocity Reduction Method to determine appropriate pipe diameters. The process begins with the smallest available size in the selected product line and iterates upward until both the maximum velocity and maximum pressure loss per meter constraints are satisfied.
Dimensioning regimes
Sizing constraints are categorized into three regimes based on the pipe diameter. While standard values are provided, users can manually edit the bound, maximum velocity, and maximum pressure loss values within the drawing settings.
| Diameter regime | Bound (mm) | Max velocity (m/s) | Max loss (Pa/m) |
|---|---|---|---|
| Small | < 15 - 22 | 0.5 - 1.0 | 300 - 360 |
| Transitional | 22 - 65 | 1.2 - 1.5 | 150 - 250 |
| Large | > 65 | 1.2 - 3.0 | 150 - 250 |
The maximum pressure loss per meter is typically constrained between 150 and 250 Pa/m.