Provides technical details on the formulas, airtightness classes, and iterative logic used to calculate air leakage in ventilation systems.
This procedure calculates air leakage and adds it to the total flow. To perform these calculations, the Calculate air leakage option must be enabled in the calculation dialog.
| Method | Description |
|---|---|
| By factor | Adds a simple percentage to the flow of every duct. This uses the "system leakage ratio" (default 5%) defined in StabiBASE. |
| By standard | Uses a formula based on the system's airtightness class. If "Custom Class" is selected, this uses the "leak factor of the custom class" (default 0.00003) from StabiBASE. |
Standard formula
The air leakage per square meter of duct surface is calculated as follows:
qvl = f · Δpm0.65
Where:
- qvl: Air leakage (m³/s per m² of duct surface)
- Δpm: The average pressure in the duct section (Pa)
- f: The leak factor, based on the selected class
Note: The formulas in DW144 (for example, 0.027 x P0.65) are in L/s/m², which corresponds to the m³/s/m² factors used in the table below.
Airtightness classes and leak factors (f)
| Airtightness Class | Leak factor (f) |
|---|---|
| Class A | 0.000027 |
| Class B | 0.000009 |
| Class C | 0.000003 |
| Class D | 0.000001 |
| Custom class | User-defined in StabiBASE |
Calculation logic (iterative process)
The calculation is a loop consisting of the following steps:
- The system pressure loss is calculated without leakage.
- The initial pressure result is used to find the average pressure (Δpm) in each duct.
- The leakage qvl is calculated for each duct using the standard formula.
- The total leakage (in m³/h) for each duct is found by multiplying qvl by the duct's surface area and converting the units.
- The leakage flow is added to the original design flow.
- The entire calculation (pressure loss, velocity) is re-run once using these new, higher flow rates.
This provides a more accurate final pressure and flow which accounts for the leakage.