Understand the core principles governing ventilation design, including duct classification, airtightness standards, flow simultaneity, and acoustic analysis.
Effective ventilation design relies on a combination of aerodynamic and acoustic calculations to ensure system efficiency and occupant comfort. By utilizing standardized duct types, designers can automatically apply pressure and velocity constraints across main runs and shafts. Furthermore, advanced calculation modules account for real-world variables such as air leakage through specific airtightness classes and flow simultaneity (Foisonnement) in residential applications. To ensure a quiet environment, acoustic algorithms track both fan noise attenuation and regenerated flow noise from the air handling unit down to the individual air terminals within a room.
Duct types in calculations
To simplify the process of applying correct design parameters, Stabicad uses duct types. When you draw a duct, you can assign it a type in its calculation properties. The following types are available:
- Connection duct: Typically used for the final run connecting a main duct to an air terminal.
- Main duct: A primary duct run that serves many connection ducts.
- Shaft duct: A vertical duct, often with different velocity and pressure constraints.
Workflow integration and behavior
- Default parameters: The default parameters for each duct type (for example, design velocity, maximum velocity, maximum pressure loss per meter) are defined in
- Application: When you assign a type to a duct (for example, main duct), the values from StabiBASE for that type are automatically applied
- Manual overwrite: You can manually overwrite any parameter for a specific duct segment after assigning a type
- Visualisation: You can use the visualise duct type functionality to see what duct has what duct type assigned
- Important behavior:
- Changing type: If you manually edit parameters on a duct and then change its type, your manual changes are replaced by the new type's defaults
- StabiBASE changes: If you change the default values in StabiBASE, these changes will not affect ducts that are already drawn in your model. The new defaults will only apply to new ducts or existing ducts that have their type changed.
Airtightness and air leakage
Air leakage is an important factor in system design, as it requires the fan to supply a higher flow rate to compensate for air lost through duct joints and connections.
- Airtightness classes: Stabicad uses the airtightness classes defined in standards like DW144 and ISSO 17. These classes (A, B, C, D) define a "leak factor" (f). The leak factor quantifies how much air a duct system is allowed to leak per square meter of surface area, relative to the pressure.
- Class A: Highest leakage (least tight).
- Class D: Lowest leakage (most tight).
- Custom class: Stabicad also allows for a "custom class" where you can define your own leak factor in (default: 0.00003).
- Calculation method: The calculation uses the selected class to determine a leak flow (in m³/s) for each duct segment based on its surface area and the average pressure within it. This leak flow is then added to the design flow, and the entire system is recalculated. This is an iterative process.
Foisonnement
Foisonnement (simultaneity), is a concept used in the French DTU 68.3 standard. It applies to systems (like residential ventilation) where it is assumed that not all air terminals will be used at their maximum capacity at the same time.
- Diversified flow: Instead of sizing main ducts for the sum of all maximum flows, the calculation uses a "diversified flow rate" (Qdf).
- k-factor: This diversified flow is calculated using a simultaneity factor (k) that decreases as the number of terminals (N) on a single path increases. For example, for 1-3 terminals, k=1.0 (100% simultaneity), but for 6 or more terminals, k=0.5 (50% simultaneity).
- Sizing logic:
- Ducts connected directly to one air terminal are sized for that terminal's maximum flow (QMf).
- All upstream ducts (main ducts, shafts) are sized for the sum of the diversified flows (Qdf) of all downstream terminals.
Acoustic calculation principles
The noise calculation determines the sound level at each air terminal and within defined rooms, measured in dB across eight octave bands (63 Hz to 8000 Hz).
- Noise in a system comes from two main sources:
- Fan noise: Noise generated by the fan (or air handling unit). This noise travels downstream and is attenuated (dampened) by ducts and fittings.
- Flow noise (Regenerated noise): Noise generated by the air itself as it moves turbulently through components like ducts, tees, bends, and valves.
- Calculation algorithm: The calculation is a "path-finding" algorithm that steps through the system from the fan to each terminal.
- It starts with the fan noise level.
- It moves downstream to the next component (for example, a duct segment).
- It calculates the noise attenuation (damping) of that component and subtracts it from the incoming noise
- It calculates the flow noise generation of that same component.
- It logarithmically adds the generated noise to the attenuated incoming noise.
- This new, combined noise level becomes the "incoming noise" for the next component in the path.
- Room calculation: You can also define rooms in your model. The calculation will sum the noise from all terminals within a room and compare it to a desired Noise Rating (NR) limit you set (e.g., "NR 35"). The result shows if the design meets the noise requirement or if additional silencing is needed.