Provides the formulas and sizing logic for "Foisonnement" (simultaneity) in ventilation systems based on the French DTU 68.3 standard.
The DTU 68.3 standard uses the concept of simultaneity for systems where air terminals are not expected to operate at maximum capacity simultaneously. To use this calculation, ensure the Appliquer Foisonnement option is enabled in the calculation dialog.
Note: The Minimum Air Flow (Qmf) and Maximum Air Flow (QMf) properties must be defined for every air terminal.
Diversified flow and simultaneity
| Calculation | Description | Formula |
|---|---|---|
| Diversified flow | Calculates the diversified flow rate (Qdf) for individual terminals. |
Qdf = k · QMf + (1 - k) · Qmf Where:
|
Simultaneity factor (k)
The k factor is determined by the total number of terminals (N) on the same flow path.
| Amount of air terminals (N) | k factor |
|---|---|
| 1-3 | 1.0 |
| 4 | 0.8 |
| 5 | 0.6 |
| 6 or more | 0.5 |
Duct sizing logic
| Duct Position | Sizing Rule |
|---|---|
| Direct connection | Ducts connected directly to an air terminal are sized using the terminal's Maximum Flow (QMf) to handle peak load. |
| Upstream | All upstream ducts (main ducts, shafts) are sized using the sum of the calculated Diversified Flows (Qdf) from all downstream terminals. |