Provides the technical formulas and information used for ventilation calculations based on ISSO 17 and ISSO 24 standards.
Duct sizing and pressure loss
| Calculation | Description | Formula |
|---|---|---|
| Duct sizing | Determines the required cross-sectional area based on design velocity. |
A = Qv / V Where:
|
| Pressure loss (Ducts) | Standard core formula for pressure difference in Dutch-based projects. |
Δp = λ · (L / D) · (1 / 2) · ρ · v² |
Friction Factors (λ)
| Flow Regime | Description | Formula |
|---|---|---|
| Laminar flow | Applied when the Reynolds number (Re) is less than 2300. |
λ = 64 / Re |
| Transition flow | Linear interpolation applied when 2300 < Re < 3500. |
λ = (λL · (3500 - Re) + λT · (Re - 2300)) / (3500 - 2300) |
| Turbulent (Normal) | Colebrook-White equation used for normal ducts when Re > 3500. |
1 / √λ = -2 · log((ε / (3.72 · D)) + (2.51 / (Re · √λ))) |
| Turbulent (Flexible) | Specific friction factor for flexible ducts. |
λ = 0.2 · 10sd · 6 · Ss · 7 Where:
|
Fittings and local resistance
| Calculation | Description | Formula |
|---|---|---|
| Normal fittings | Calculates loss for bends, reducers, and tees using a zeta factor. |
Δp = ζ · (1 / 2) · ρ · v² Where:
|
| Special fittings | Used for non-standard fittings like under-floor pots. |
ζ = ζref · (Re / 30000)n Where:
|
This calculation determines noise generation and attenuation in dB per octave band from 63 Hz to 8000 Hz. To use this feature, the Calculate noise checkbox must be enabled.
Noise generation formulas
| Component | Description | Formula |
|---|---|---|
| Fan | Calculates the base noise power level generated by the fan. |
Lwb = 40 + 20 · log(ΔP) + 10 · log(qv) + Cr Where:
|
| Straight duct | Calculates regenerated flow noise for linear segments. |
Lwb = 7 + 50 · log(v) + 10 · log(S) Where:
|
| Tees and bends | Calculates flow noise generated by bent branches or elbows. |
Lw = Lw1 + 10 · log(Δf) + 30 · log(da) + 50 · log(va) + k Where:
|
| Air terminal or valve | Calculates noise power based on flow and local resistance. |
Lwb = 10 + 60 · log(qv) - 50 · log(S) + 30 · log(ζ) Where:
|
Room noise and required silencing
| Calculation | Description | Formula |
|---|---|---|
| Terminal noise in room | Determines the noise from an individual terminal as heard in the room. |
LAT_final(i) = LAT_total(i) - Droom Where:
|
| Total room noise | Logarithmic sum of noise from all terminals within a defined room. |
Lroom = 10 · log(Σ 10(LAT_final(i) / 10)) |
| Required silencing | The final result comparing room noise to the design limit. |
Lsilencer = Lroom - NR Where:
NOTE: If Lsilencer is positive, a silencer with that amount of attenuation is required to meet the design goal. |