ISSO 17 and ISSO 24 formulas (NL)

Modified: 29 Jun 2026 Stabicad
Stabicad
Stabicad

Provides the technical formulas and information used for ventilation calculations based on ISSO 17 and ISSO 24 standards.

Duct sizing and pressure loss

Calculation Description Formula
Duct sizing Determines the required cross-sectional area based on design velocity.

A = Qv / V

Where:

  • A: Cross-sectional area (m²)
  • Qv: Flow (m³/s)
  • V: Design velocity (m/s)
Pressure loss (Ducts) Standard core formula for pressure difference in Dutch-based projects.

Δp = λ · (L / D) · (1 / 2) · ρ · v²

Friction Factors (λ)

Flow Regime Description Formula
Laminar flow Applied when the Reynolds number (Re) is less than 2300.

λ = 64 / Re

Transition flow Linear interpolation applied when 2300 < Re < 3500.

λ = (λL · (3500 - Re) + λT · (Re - 2300)) / (3500 - 2300)

Turbulent (Normal) Colebrook-White equation used for normal ducts when Re > 3500.

1 / √λ = -2 · log((ε / (3.72 · D)) + (2.51 / (Re · √λ)))

Turbulent (Flexible) Specific friction factor for flexible ducts.

λ = 0.2 · 10sd · 6 · Ss · 7

Where:

  • s: Wall thickness
  • S: Wave length

Fittings and local resistance

Calculation Description Formula
Normal fittings Calculates loss for bends, reducers, and tees using a zeta factor.

Δp = ζ · (1 / 2) · ρ · v²

Where:

  • ζ (zeta): Resistance coefficient based on geometry.
Special fittings Used for non-standard fittings like under-floor pots.

ζ = ζref · (Re / 30000)n

Where:

  • ζref and n: Geometry-specific factors from ISSO 17.
Note: For fitting dimensions not explicitly defined in ISSO 17, Stabicad applies parameters from the closest available dimension as an estimation.

This calculation determines noise generation and attenuation in dB per octave band from 63 Hz to 8000 Hz. To use this feature, the Calculate noise checkbox must be enabled.

Noise generation formulas

Component Description Formula
Fan Calculates the base noise power level generated by the fan.

Lwb = 40 + 20 · log(ΔP) + 10 · log(qv) + Cr

Where:

  • ΔP: System pressure (Pa)
  • qv: Total flow (m³/s)
  • Cr: Correction factor for fan efficiency
Straight duct Calculates regenerated flow noise for linear segments.

Lwb = 7 + 50 · log(v) + 10 · log(S)

Where:

  • v: Velocity (m/s)
  • S: Cross-sectional area (m²)
Tees and bends Calculates flow noise generated by bent branches or elbows.

Lw = Lw1 + 10 · log(Δf) + 30 · log(da) + 50 · log(va) + k

Where:

  • Lw1: Standardized noise power from ISSO tables
  • da: Hydraulic diameter (m)
  • va: Velocity (m/s)
Air terminal or valve Calculates noise power based on flow and local resistance.

Lwb = 10 + 60 · log(qv) - 50 · log(S) + 30 · log(ζ)

Where:

  • qv: Flow (m³/s)
  • S: Area (m²)
  • ζ: Zeta factor

Room noise and required silencing

Calculation Description Formula
Terminal noise in room Determines the noise from an individual terminal as heard in the room.

LAT_final(i) = LAT_total(i) - Droom

Where:

  • LAT_total(i): Total noise from terminal i (dB)
  • Droom: User-defined "Noise attenuation of room" (dB)
Total room noise Logarithmic sum of noise from all terminals within a defined room.

Lroom = 10 · log(Σ 10(LAT_final(i) / 10))

Required silencing The final result comparing room noise to the design limit.

Lsilencer = Lroom - NR

Where:

  • NR: The desired Noise Rating limit

NOTE: If Lsilencer is positive, a silencer with that amount of attenuation is required to meet the design goal.