Provides the technical formulas, material roughness values, and pressure loss logic used for ventilation calculations based on CIBSE Guide C and DW144 standards.
Pressure loss and friction factors
| Calculation | Description | Formula |
|---|---|---|
| Pressure loss (Ducts) | Core pressure loss formula for UK-based projects |
Δp = λ · (l / d) · (1 / 2) · ρ · c² Where:
|
| Friction factor (Laminar) | Applied when the Reynolds number (Re) is less than 2000 |
λ = 64 / Re |
| Friction factor (Turbulent) | Haaland equation used when Re is greater than 3000, as recommended by CIBSE |
1 / √λ = -1.8 · log[(6.9 / Re) + ((k / d) / 3.71)^1.11] Where:
|
Equivalent roughness (k)
| Material | Roughness (k) [mm] |
|---|---|
| Abs / Plastic / PVC | 0.007 |
| Copper | 0.015 |
| Stainless steel | 0.04 |
| Aluminium / Steel | 0.05 |
| Galvanized | 0.15 |
| Flexible | 4.6 |
Fittings, equipment, and sizing logic
| Method/logic | Description | Calculation behavior |
|---|---|---|
| Default standard (Fittings) | Uses ζ (zeta) based logic from ISSO 17 / CIBSE. | Includes detailed calculations for bends in close proximity and tee + reducer combinations. |
| Fitting pressure loss factor | Simplified estimation method that skips ζ calculations. | Calculated as a user-defined percentage of the total duct pressure loss. The report displays a ΔP factor column. |
| Flexible duct sizing | Special logic applied when "Recalculate existing diameters" is enabled to avoid unnecessary reducers. | Stabicad forces the flexible duct diameter to match the connected rigid duct, even if the resulting loss exceeds the "Maximum pressure loss per meter" constraint. |