Waste water calculation concepts

Modified: 6 May 2026 Stabicad
Stabicad
Stabicad

Understand the functional scope, system requirements, and pipe classifications required to perform hydraulic sizing and flow calculations for gravity-based waste water systems.

Waste water calculations in Stabicad provide an automated method for sizing gravity-based sanitary systems based on international technical standards. The engine analyzes model connectivity and slope to determine peak flow rates and assign functional roles to system segments, ensuring that your MEP design meets regional regulatory constraints for drainage and ventilation.

Supported waste water standards

Stabicad supports localized calculations for waste water systems. Selecting a specific standard in StabiBASE > Sewerage > Calculation updates the available parameters and calculation logic to align with regional requirements.

Standard Region
BS EN 12056 (2000) United Kingdom
NTR 3216 (2012) Netherlands
DIN 1986-100 (2016) Germany
DTU 60.11 (2013) France
EN 12056 (2000) Europe

Calculation scope

The waste water module performs hydraulic sizing and flow calculation for gravity-based waste water systems. The calculation functionality includes the following features:

Feature Description
Flow determination Calculates peak flow based on connected appliances and simultaneity.
Dimensioning Automatically sizes pipes based on flow, slope, and standard-specific constraints.
Pipe type identification Automatically recognizes different functional roles for pipes (for example, stack versus drain).

System requirements

To perform a successful waste water calculation, your model must meet specific connectivity and configuration criteria. Ensure the following requirements are satisfied before launching the calculation engine:

Criterion Requirement
Connectivity The system must be fully connected with defined consumers (sanitary equipment) and contain exactly one discharge endpoint.
Slope Pipes must have a defined slope, which can be physically drawn in the model or specified within the calculation properties of the system endpoint.
Standard selection An active calculation standard must be selected in StabiBASE to provide the necessary regional logic and parameters.

Waste water pipe type classification

The waste water calculation engine identifies pipes within a system based on their functional role. This classification is critical because it determines which specific hydraulic sizing rules and constraints are applied to each segment.

Pipe type Description
Connection pipe Connects a single sanitary appliance to a branch, stack, or drain.
Branch pipe A horizontal pipe that collects discharge from multiple individual connection pipes.
Stack pipe A main vertical conduit that collects waste water discharge from multiple floors.
Drain pipe A main horizontal pipe that receives water from all other system pipes, typically leading to a public sewer.
Ventilation pipes Pipes utilized for gas emission and pressure equalization, including stack vents, ventilating stacks, or branch ventilation.

Standard switching behavior

When you switch calculation standards in StabiBASE > Sewerage > Calculation (for example, from EN to NTR), the application manages existing data based on the following logic:

Data type Behavior during standard switch
Unaltered flows System flows that have not been modified will automatically update to the default values of the newly selected standard.
User overrides Flow rates that were manually edited by the user are preserved and will not be overwritten by the new standard's defaults.
Unique equipment Equipment that is only available in the previous standard will remain in the project but will be displayed with the original standard's name in parentheses (for example, "(Standard A)").