Stabicad

Provides the core concepts and separation requirements for waste water systems based on the French DTU 60.11 standard.

Separation of waste water (Noir versus Gris)

A fundamental requirement of the DTU 60.11 standard is the strict separation of waste water types within the building:

Waste water type Description
Eaux vannes (Noir/Black water) Waste water from toilets (WCs)
Eaux ménagères (Gris/Grey water) Waste water from sinks, showers, baths, and appliances

The rule of separation:

These two water types must be carried by separate stack pipes. They are only permitted to merge in the drain pipe (horizontal collector) before leaving the building. The Stabicad algorithm validates this separation.

Pipe role identification

Stabicad identifies pipes based on their role in the system:

Pipe role Standard description
Connection pipe (Branchement) Connects one or more appliances to a branch or stack.
Branch pipe (Collecteur d’étage) Horizontal pipe collecting multiple connections.
Stack pipe (Chute/Descente) Vertical pipe. In DTU, these are specifically identified as Chute d'eaux vannes or Descente d'eaux ménagères.
Drain pipe (Collecteur principal) The horizontal main leading to the sewerage endpoint.

Connection pipes and the "bath length" rule

Connection pipes are sized based on the appliance type. A unique DTU rule applies to baths:

Bath length Minimum internal diameter
Length ≤ 1.0 m Requires a minimum internal diameter of 33 mm (Standard DN 40)
Length > 1.0 m Requires a minimum internal diameter of 38 mm (Standard DN 50)

Stack pipe sizing

DTU 60.11 defines minimum diameters for stacks to ensure proper ventilation and prevent siphonage:

Water type Minimum diameter requirement
Eaux vannes (Noir) Minimum DN 100 (internal diameter ≥ 90 mm)
Eaux ménagères (Gris) Minimum DN 65 or 75 depending on the number of floors and appliances

Branch pipe (horizontal) sizing

For horizontal branches, sizing is determined by the total flow (Qtot):

Total flow (Qtot) Dimensioning rule
Qtot ≤ 2.5 l/s Dimensioned according to standard branch lookup tables
Qtot > 2.5 l/s Dimensioned according to drain pipe rules (collector), which requires a minimum slope and utilizes different filling degree capacities

Drain pipe sizing

Drain pipes are sized based on the slope and the water type:

Water condition Sizing rule
Separated water Sized using the 50% filling degree table
Mixed water Sized using the 70% filling degree table once Noir and Gris water have merged