Provides the core concepts and separation requirements for waste water systems based on the French DTU 60.11 standard.
Separation of waste water (Noir versus Gris)
A fundamental requirement of the DTU 60.11 standard is the strict separation of waste water types within the building:
| Waste water type | Description |
|---|---|
| Eaux vannes (Noir/Black water) | Waste water from toilets (WCs) |
| Eaux ménagères (Gris/Grey water) | Waste water from sinks, showers, baths, and appliances |
The rule of separation:
These two water types must be carried by separate stack pipes. They are only permitted to merge in the drain pipe (horizontal collector) before leaving the building. The Stabicad algorithm validates this separation.
Pipe role identification
Stabicad identifies pipes based on their role in the system:
| Pipe role | Standard description |
|---|---|
| Connection pipe (Branchement) | Connects one or more appliances to a branch or stack. |
| Branch pipe (Collecteur d’étage) | Horizontal pipe collecting multiple connections. |
| Stack pipe (Chute/Descente) | Vertical pipe. In DTU, these are specifically identified as Chute d'eaux vannes or Descente d'eaux ménagères. |
| Drain pipe (Collecteur principal) | The horizontal main leading to the sewerage endpoint. |
Connection pipes and the "bath length" rule
Connection pipes are sized based on the appliance type. A unique DTU rule applies to baths:
| Bath length | Minimum internal diameter |
|---|---|
| Length ≤ 1.0 m | Requires a minimum internal diameter of 33 mm (Standard DN 40) |
| Length > 1.0 m | Requires a minimum internal diameter of 38 mm (Standard DN 50) |
Stack pipe sizing
DTU 60.11 defines minimum diameters for stacks to ensure proper ventilation and prevent siphonage:
| Water type | Minimum diameter requirement |
|---|---|
| Eaux vannes (Noir) | Minimum DN 100 (internal diameter ≥ 90 mm) |
| Eaux ménagères (Gris) | Minimum DN 65 or 75 depending on the number of floors and appliances |
Branch pipe (horizontal) sizing
For horizontal branches, sizing is determined by the total flow (Qtot):
| Total flow (Qtot) | Dimensioning rule |
|---|---|
| Qtot ≤ 2.5 l/s | Dimensioned according to standard branch lookup tables |
| Qtot > 2.5 l/s | Dimensioned according to drain pipe rules (collector), which requires a minimum slope and utilizes different filling degree capacities |
Drain pipe sizing
Drain pipes are sized based on the slope and the water type:
| Water condition | Sizing rule |
|---|---|
| Separated water | Sized using the 50% filling degree table |
| Mixed water | Sized using the 70% filling degree table once Noir and Gris water have merged |