BS EN 12056 system types and constraints (UK/Europe)

Modified: 7 May 2026 Stabicad
Stabicad
Stabicad

Provides the specific design rules, system types, and pipe dimensioning constraints for gravity drainage systems based on the BS EN 12056 standard.

Calculation scope

The BS EN 12056 standard defines the design and calculation of gravity drainage systems inside buildings. Stabicad implements Part 2: Sanitary pipework, layout, and calculation.

System types (I to IV)

The standard recognizes four distinct system types based on the filling degree of the pipes and the configuration of the discharge:

System type Description
System I (Single discharge stack system) Branch pipes are designed to a filling degree of 0.5 (50%). It uses a single stack for all waste water.
System II (Single discharge stack system) Branch pipes are designed to a filling degree of 0.7 (70%), allowing for smaller pipe diameters.
System III (Single discharge stack system) Currently not supported in Stabicad.
System IV (Separate stack system) Utilizes separate stacks for black water (toilets) and grey water (sinks/showers).

Pipe role identification

The Stabicad algorithm automatically identifies the function of a pipe to apply the correct sizing table:

  • Connection Pipe: From a single appliance to a branch or stack
  • Branch Pipe: Horizontal pipe collecting multiple connection pipes
  • Stack Pipe: Vertical main pipe
  • Drain Pipe: The horizontal main leading to the exit (Sewerage Endpoint)

Branch pipes (horizontal)

Sizing for branches depends on whether they are ventilated or unventilated.

Branch type Description and limitations
Unventilated branches Capacity is limited to prevent siphonage of traps. Limitations include a maximum number of bends (usually 3) and a maximum length (for example, 10m for System I).
Ventilated branches Connected to a branch ventilating pipe, allowing for higher flow capacities and longer runs.

Toilet constraints:

  • For System II and IV, no toilets can be attached to DN 70 or smaller unventilated branches if Qmax = 2.0 l/s
  • Only one toilet may be attached to a DN 80 unventilated branch
  • Two or more toilets require a minimum of DN 90

Stack pipes (vertical)

The capacity of a stack is governed by the type of ventilation and the type of inlet branch connection:

  • Primary ventilation: The stack vent is an extension of the discharge stack to the atmosphere.
  • Secondary ventilation: A separate, parallel ventilating stack is connected to the discharge stack at each floor to relieve pressure.

Square vs. swept entries:

The geometry of the connection between a branch and a stack affects capacity:

  • Square entry: 90° Tee with lower capacity due to increased turbulence.
  • Swept entry: A curved connection (radius) or 45° entry with high capacity as flow enters smoothly.

Drain pipes

Drain pipes are dimensioned based on the Slope (i) and the Filling Degree (h/d):

  • Standard filling degrees are 0.5 or 0.7, which can be set in the endpoint.
  • Calculations are performed against tables defining Qmax for specific slopes (for example, 1%, 2%).