Precalculate the required dimensions of a duct based on airflow requirements, maximum velocity, and connected grilles before placing the duct in your project.
Before you start, ensure you have started drawing a system.
You can calculate duct dimensions based on input parameters (flow rate or connected grilles) and the maximum allowed velocity. This helps you ensure the duct is correctly sized for the design requirements.
Note: The procedure differs depending on if you are using AutoCAD or Revit.
- Open the Duct Slide Rule dialog.
- If using AutoCAD: While actively drawing a duct, right-click and select Duct Slide Rule.
- If using Revit: In the Select pipe dialog, click the calculator icon
in the header of the Diameter, Width, or Height columns.
- In the Duct Slide Rule dialog, enter the required duct flow, or click the grille icon
to select a grille to connect the duct to.
You can add or remove grilles from the selection.
Note:
You can lock one dimension of a rectangular or oval duct before adding or removing grilles. This keeps the dimension fixed while altering the other to meet the velocity constraint.

- Choose the duct type (Connection duct, Main duct, or Shaft), and enter its maximum speed.
- In the Calculated minimum dimensions section, review the calculated dimensions.
- In the Selected dimensions section, choose the final shape and dimensions of the duct to draw.
- Click OK.
You can recalculate the dimensions for remaining grilles after connecting the duct to one grille by repeating the procedure.