Use predefined view templates and parameter-based filters to standardize model visibility and streamline multi-disciplinary coordination.
Standardized view templates and filters ensure that your model displays the right information for each MEP sub-discipline. By leveraging NL-SfB encoding and automated parameters like FUNCODE, you can isolate systems, gray out background architecture, or apply temporary overrides for easier coordination.
Templates for views
The standard view templates are used by the Create Plan Views tool in StabiTOOLS. The filtering logic is based on the NL-SfB encoding system.
- Custom templates - To make your own view templates visible in the Create Plan Views tool, you need to rename them to start with the
S4R_prefix. - Depth clipping - The default depth clipping is Clip without line, allowing elements cut by the view range to extend below it.
Architectural and coordination views
| Template | Description |
|---|---|
| A00_General | Displays architectural and structural elements from the model and linked files. MEP elements are hidden unless they are "in-sight" fixtures (for example, lighting). |
| C00_Coordination | Displays all disciplines simultaneously to identify interferences between architectural, structural, electrical, and mechanical elements. |
Electrical views
| Template | Description |
|---|---|
| E60_General | Displays all electrical elements in the model. |
| E61_Central Facilities | Displays cable trays, ladders, conduits, and distribution panels. |
| E62_Power Current | Displays wall sockets, connection points, and consumers (230V/400V). |
| E63_Lighting | Displays lighting fixtures, switches, and emergency/exit lighting. |
| E64_Communication | Displays communication devices, including data/phone sockets and patch panels. |
| E65_Security | Displays security-related systems (CCTV, access control, fire alarms). |
Mechanical views
| Template | Description |
|---|---|
| M50_General | Displays all mechanical systems in the model. |
| M50_Piping | Displays all piping systems (excludes ventilation/ductwork). |
| M52_Piping Sewerage | Displays sewerage and rainwater drainage. |
| M53_Piping Sanitary | Displays sanitary components, domestic water, gas, and sewerage. |
| M54_Piping Gas | Displays technical and medical gas systems. |
| M56_Piping Climate | Displays climate-related hydronic systems (supply and return). |
| M57_Ventilation | Displays Air Terminals, ductwork, accessories, and air handling units. |
| M65_Sprinkler | Displays all sprinkler systems and heads. |
Filtering principles for discipline-specific views
The view templates in the Revit template are optimized to filter elements created with Stabicad. Since NL-SfB codes do not map directly to Revit categories, the template relies on two parameter-based rules to control visibility.
Electrical components (Rule A)
Electrical components include a FUNCODE instance parameter. This field is populated automatically with the character "E" followed by the four-digit NL-SfB code. You can apply filters using two-digit (subdomain) or four-digit (domain-specific) logic. The following are examples of electrical filters:
| Filter Rule | Result |
|---|---|
| FUNCODE [contains] E63 | Displays all lighting components in the model. |
| FUNCODE [contains] E6350 | Displays all decentralized emergency lighting components. |
Mechanical components (Rule B)
Mechanical elements are filtered via the System Abbreviation parameter found in the System Browser. Stabicad populates this field with the character ‘M’, the four-digit NL-SfB code, and optional specification codes (e.g., F for Feed, R for Return). The following are examples of mechanical filters:
| Filter Rule | Result |
|---|---|
| System Abbreviation [contains] M54 | Displays all gas systems in the model. |
| System Abbreviation [contains] M544 | Displays all technical gas systems. |
| System Abbreviation [contains] M5448FR | Displays only Freon return systems. |
Discipline override and utility filters
| Filter Name | Function and Application |
|---|---|
| S4R_Architectural |
|
| S4R_Electrical |
|
| S4R_Mechanical |
|
| S4R_Filter_Custom_Elements |
|
| S4R_Filter_Non_Stabicad_Elements |
|