EC1991 1-4 Wind Zones

Modified: 5 Mar 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer

At the end of the Wind Wizard, the system creates default zones in the Wind window for all the walls and roof panels for each of the defined wind directions.

If any errors have occurred in this process, a red cross appears next to Pressure Zones in the Wind window.

Basic Geometry

The basic building geometry is assessed as follows:

  • Reference Height (ze) - is taken as the difference between highest point on wall or roof panel and ground level.
  • Wall height (h) - is taken as the difference between highest and lowest points on the wall panel.

    These definitions apply to wall panels without parapets and the actual parapets. Wall panels with parapets above them will take their highest point from the parapet. See the diagram below.

  • Roof height (h) - as ze - taken as the difference between highest point on wall or roof panel and ground level. This definition does not handle the upper roof of inset storey but is conservative.
  • The Building Breadth, b is calculated from the smallest enclosing rectangle around the whole building (considered over all roof and wall panels only) for the given direction. You can override the calculated value in case the Tekla Structural Designer model does not include the whole building.

Wall Zones

Wall Type

We assess each wall panel to determine if it is a windward, leeward or side wall. We classify the type of wall dependent on q:

  • θ ≤ 60 deg - Windward,
  • θ ≥ 120 deg - Leeward,
  • Other walls are classed as Side.
Windward walls Windward walls have a single zone and Table 7.1 is used with interpolation for h/d.
Leeward walls Leeward walls have a single zone and Table 7.1 is used with interpolation for h/d.
Side walls In all cases, side walls have the relevant number of zones from Figure 7.5 and Table 7.1 is used.

There is no guidance in the standard for Irregular Flushed Faces, Recesses and Downwind Re-entrant Corners that are covered in BS6399. However, it is reasonable to automatically detect Irregular Flushed Faces and process them as described in BS6399 Clause 2.4.4.1 and Figure 14. The program also detects potential Recesses but only generates a warning and no special handling occurs. Downwind re-entrant corners are conservatively ignored.

Parapets

Parapets are assessed for return corners and then classified as windward, windward oblique, leeward or leeward oblique dependent on q.

Depending on the classification, parapets will either have a single zone, or up to seven zones (determined by extrapolation from Figure 7.19). Table 7.9 is used with interpolation for Solidity and l/h.

Note: An "r" suffix on zone name indicates return corners have been detected.

Side Parapets are Special Zero zones, i.e. no nett pressure.

Roof Zones

Roof zones are automatically generated where possible for each wind direction. In essence each roof panel is assessed in its own right based on its properties. The interconnectivity of touching roof panels is not generally considered.

Direction

Internally the roof slope vector (line of maximum slope) is determined from the normal vector, with its direction always giving a positive slope angle, i.e. the roof slope vector must always point up the slope.

We calculate the angle between the wind direction and projection of roof slope vector onto horizontal plane ( q in range -180° to +180°).

Scaling Dimension, e

The scaling dimension e = min(b, 2h)

Automatic Zoning

Automatic zoning normally only applies to all triangular roof panels and quadrilateral roof panels that are not concave, that is that all of the internal angles < 180°. However, additionally, it only applies to Hip Gable roofs if they are triangular, and Hip Main roofs if they are quadrilateral. Further, Downwind Slope Hip Gables must not have 2 upwind corners.

Multibay Roofs

We allow you to manually define the roof types as you think appropriate. You also have the ability to manually set the Bay Cpe Multiplier for each roof panel for each wind direction:

  • Not Multibay - for this wind direction (conservative default),

  • Bay Factor = 1.0 - for this wind direction,

  • Bay Factor = 0.8 - for this wind direction,

  • Bay Factor = 0.6 - for this wind direction.

The above Bay Factors are determined according to Figure 7.10.

Non-Automatic Zoning

Where automatic zoning does not apply, the system creates a single zone covering the entire roof as follows:

  • Hip Gable - B for upwind, B for downwind, D for side,

  • Flat - B,

  • Monopitch - B,

  • Duopitch - B for upwind, A for downwind, B for side,

  • Hip Gable - B for upwind, B for downwind, D for side,
  • Hip Main - B for upwind, A for downwind, D for side.

Override Wind Zone Cpe & Cpi values

Note:

In order to override Cpe and Cpi values, you must have already created wind loadcases.

Edit the Cpi value of a zone

  1. Open a Wind view and display the Zone loads. You will need to have a wind loadcase selected in the Loading list.

  2. Click to select a zone in the model and in the Properties window you can untick the “Default” property which will allow you to override the Cpi value.

Edit the Cpe values

  1. Open a Wind view and display the Zone loads. You will need to have a wind loadcase selected in the Loading list.

  2. Right-click over a Roof or Wall panel in the Wind Model tree and choose the option Edit Zones... from the context menu.

  3. Uncheck the "Std." (Standard) check box for the zone(s) you wish to edit - you can then enter your own value(s) of Cpe

  4. Repeat for other panels/ Wind directions as required.

Specify Bay Cpe Multipliers for Multibay roofs

  1. Open a Wind view and select Multibay.

  2. Click to select a roof panel in the model and in the Properties window you can change the Bay Cpe Multiplier from the default of "Not Multibay" to an appropriate “bay factor.

  3. Repeat for other panels/ Wind directions as required.