Footfall analysis limitations and assumptions

Modified: 17 Jul 2023 Tekla Structural Designer 2025
2025
Tekla Structural Designer

Tekla Structural Designer can perform footfall assessments to:

  • UK practice - using the SCI P354 design guide, or the CCIP-016 design guide.
  • US practice - using the AISC DG11 design guide
Note:
If when following UK practice, the same model were to be assessed in Tekla Structural Designer to both the SCI P354 design guide and the CCIP-016 design guide; while the underlying modal analysis results will be identical, there can be significant differences in the footfall check results. This is due to differences in the approaches adopted by the two guides to post process the modal analysis results. For a small number of comparison models it seems that the response calculated to CCIP-016 tends to be lower than when using SCI P354, and that the difference tends to be greater for transient than for resonant response calculations. Two additional points may be worth considering in this regard:
  1. The SCI P354 guide includes suggestions that the limits applied can be relaxed in normal situations. Perhaps this more relaxed view should only apply when the response factors are calculated using the SCI guide.
  2. The SCI P354 guide permits a VDV assessment for both resonant and transient responses while the CCIP-016 design guide restricts VDV to resonant responses only. Therefore, the higher transient responses determined using the SCI Guide may not be limiting.

Assumptions

  • The SCI P354 guidance includes forcing functions due to walking that are either continuous or intermittent. Floor behavior is categorized as low frequency, 0 to 10 Hz, or high frequency, > 8Hz. These are classed as steady state or transient responses respectively and fit neatly with the continuous and intermittent forcing functions. The industry recommendation is to calculate both forcing functions when the floor is nominally classed as low frequency. So both are implemented.

  • Excitation and response positions are assumed to be coincident.

  • Summing accelerations most commonly uses square root of sum of squares (SRSS) and these are offered in the first release.

  • Non-continuous response using techniques such as Vibration Dose Value (VDV) are adopted but for greater ease of use the calculation procedure is ‘inverted’ to provide the number of times the walking path would need to be executed in order to generate an adverse response.

  • If precast slabs with reinforced structural topping and with studs to supporting beams are defined, these contribute fully to the modal mass used in the vibration analysis. The mass is determined from the given ‘Weight per units area’ of the pc plank plus a calculated allowance for the topping. The role of primary beams in this situation is unclear as they tend not to have studs but are usually joined with infill concrete. The assumption taken is that their self-weight is included. This is reasonable if you ask for the precast slabs to be meshed in Settings. But if they are not at all composite, as noted in SCI P354 Section 4.1.6, caution is advised.

Limitations

  • Steel Plate, timber, and other general material floor areas can be included in the FAM primarily so that the response of the supporting structure can be considered. However, if working to SCI P354, since the guidance is almost entirely based on steel buildings with composite or precast floors, if the option is taken to mesh such slab areas the results should be viewed with caution.

  • For Westok beams the self weight is adjusted to allow for the cells but for other beams with web openings the full section is used. Thus for Westok beams, the correct mass is determined for the modal analysis. On the other hand for beams with web openings whilst the full self weight of the unperforated section is used for beam design and this is conservative, for modal analysis this is not conservative. However, given the small proportion of the floor mass that this represents, the degree of unconservatism introduced by using the full self weight is unlikely to be significant.

  • If working in the US (ACI/AISC) Region, Steel Joists can be included in the FAM, but will have the analysis properties used in general analysis and fixed ends (or not) as specified in model settings.

  • DG11 requires that where transfer or ‘hanger’ columns are attached to the floor under consideration then the floor above should also be included in the FAM. This is excluded in the current release.

  • If tension/compression only braces are included they are treated as linear.

  • Trusses are effectively dealt with as fixed lines of support - this is not suggested to be correct or ideal, it simply allows flexibility. For example slab areas one panel remote from the truss can be considered quite reasonably.

  • Shear only walls are excluded from the FAM (but this does not make the FAM invalid).

    • Basically these walls are intended only to provide lateral stability, FAMs tend to be inherently laterally stable due to fixed member ends etc.