The check for sliding is carried out for pad foundations only.
If there is no horizontal force acting on foundation, check for sliding is not required.
Sliding resistance (EC7 Section 6.5.3) - forces are defined from STR combinations.
Horizontal forces on foundation for each direction:
Fdx = Fx,sup
Fdy = Fy,sup
where
- Fx,sup = factored horizontal force acting on support in X-dir. (from analysis)
- Fy,sup = factored horizontal force acting on support in Y-dir. (from analysis)
Horizontal force on foundation:
Hd = [|Fdx|2 + |Fdy|2]0.5
Sliding resistance verification (Section 6.5.3)
Sliding resistance (exp. 6.3b and Table A.5):
RH,d = [FzG,d + γGf · Fswt] · tan δk / γR,h
where
- δk = factored horizontal force acting on support in X-dir.
- γR,h = 1.1 (Set R2): EC7 recommendations and for Irish and Malaysian NA
- γR,h = 1.0 (Set R1): for UK and Singapore NA
- γGf = 1.0 (permanent favorable action)
- FzG,d = vertical load acting on support in STR/GEO limit states where favorable actions are considered