Checks for limiting parameters (pad and strip base: ACI 318)

Modified: 9 Nov 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer

Limiting reinforcement parameters are specified in Design Settings > Concrete > Cast-in-place > Foundations > Isolated Foundations > Reinforcement Layout.

Limits on Bar Size and Reinforcement Quantities

For structural foundations of uniform thickness the minimum area of tensile reinforcement shall be:

For metric units:

If Grade 280 to 350 deformed bars are used:

As,min,reqd ≥ b · h · 0.0020

If Grade 350 to 420 deformed bars or welded wire reinforcement are used:

As,min,reqd ≥ b · h · 0.0018

If yield stress exceeds 420 MPa:

As,min,reqd ≥ b · h · max(0.0014, 0.0018 · 420 MPa / fy)

For US units:

If Grade 40 to 50 deformed bars are used:

As,min,reqd ≥ b · h · 0.0020

If Grade 50 to 60 deformed bars or welded wire reinforcement are used:

As,min,reqd ≥ b · h · 0.0018

If yield stress exceeds 60000 psi:

As,min,reqd ≥ b · h · max(0.0014, 0.0018 · 60000 psi / fy)

where b = unit width

The maximum area of tensile reinforcement is:

As,max ≤ 0.85 · (f'c / fy) · β1 · b · d · (3/7)

where

  • Ag = gross area of the concrete section
  • β1 = stress block depth factor1

For metric units:

β1 = 0.85 for f'c ≤ 28 MPa

β1 = 0.85 − 0.05 · [(f'c − 28 MPa) / 7 MPa] for 28 MPa < f'c < 55 MPa

β1 = 0.65 for f'c ≥ 55 MPa

For US units:

β1 = min(max(0.85 − 0.05 · (f'c − 4 ksi) / 1 ksi, 0.65), 0.85)

β1 = 0.85 for f'c ≤ 4000 psi

β1 = 0.85 − 0.05 · [(f'c − 4 ksi) / 1 ksi] for 4000 psi < f'c < 8000 psi

β1 = 0.65 for f'c ≥ 8000 psi

Footnotes

1 ACI 318-08, ACI 318-11, ACI 318M-08 and ACI 318M-11 Section 10.2.7.3