Check for transfer forces at column base (pad and strip base: ACI 318)

Modified: 9 Nov 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer

This check applies when a concrete column is attached to the foundation.

Determine the bearing strength of the column:

ϕ · Pnb,c = ϕbearing · (0.85 · f'c · Ac)

If ϕ · Pnb,c < −Pu:

then check fails,

else determine the bearing strength of the footing:

ϕ · Pnb,f = min[√(A2 / Ac), 2] · ϕbearing · (0.85 · f'c · Ac)

where for rectangular columns: A2 = min{Lx, 2 · tftg + lx + min[(Lx − lx) / 2 − |ex|, 2 · tftg]} · min{Ly, 2 · tftg + ly + min[(Ly − ly) / 2 − |ey|, 2 · tftg]}

Note:

Circular columns are treated as square members with the same area.

If ϕ · Pnb,f < −Pu:

then check fails.

Required minimum area of dowel bars between column and footing is then:1

As,min = 0.005 · Ac

Currently dowel bars are not designed.

The area of the provided column reinforcement, As,prov,column, is the same as the provided reinforcement of starter/dowel bars.

If As,min > As,prov,column:

then check fails.

Footnotes

1 ACI 318-08 Section 15.8.2.1