Design parameters for longitudinal bars (concrete slab: EC2)

Modified: 9 Nov 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer

For each of these parameters, any user defined limits (as specified in Design Settings > Concrete > Cast-in-place > Slab > Reinforcement Layout) are considered in addition to the EC2 or NA recommendations.

Minimum diameter of reinforcement

The minimum diameters of reinforcement are set by the user in Design Settings, the initial default values being:

Slab on Beams = 8 mm

Flat slab = 8 mm

If the design results in a bar size less than the user specified limits the checks fails.

Maximum diameter of reinforcement

The maximum diameters of reinforcement are set by the user in Design Settings, the initial default values being:

Slab on Beams = 16 mm

Flat slab = 25 mm

If the design results in a bar size greater than the user specified limits the checks fails.

Minimum distance between bars

The minimum clear horizontal distance between individual parallel bars, scl,min, is given by:1

scl,min ≥ max[k1 · φ, dg + k2, scl,u,min, 20 mm]

where

  • k1 = the appropriate NDP
  • k2 = the appropriate NDP
  • dg = the maximum size of aggregate
  • φ = the maximum diameter of bars in the layer
  • scl,u,min = user specified minimum clear distance between bars

    (default 100 mm in “Slab on Beams” and 50 mm in “Flat Slab”)

For design in accordance with:
  • EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA, Swedish NA:

    k1 = 1.0

  • Norwegian NA:

    k1 = 2.0

For design in accordance with:
  • EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Norwegian NA, Swedish NA:

    k2 = 5.0 mm

  • Finnish NA:

    k2 = 3.0 mm

Maximum spacing of tension bars (all slabs)

In accordance with clause 7.3.3(1) of EC2 for slabs not exceeding 200 mm in overall depth and not subjected to significant axial tension the maximum limit on centre to centre bar spacing is governed by clause 9.3 only and there is no need to perform specific checks on the bar spacings to control cracking. These limits are applied to all slabs and then the additional limit in the next section are applied to slabs greater than 200 mm thick.

From clause 9.3 the maximum limit on bar spacings can be somewhat subjective so these limits are user definable with conservative defaults as follows:

Principal bars (NDP) (cl. 9.3.1.1(3))

smax = 2 · h but ≤ 250 mm

Secondary bars (NDP) (cl. 9.3.1.1(3))

smax = 3 · h but ≤ 400 mm

Bars are classed as secondary if both the following are true:

  1. The design moment for bars in this direction is lower than the design moment for bars in the other direction.
  2. The calculated reinforcement requirement based on the design moment is less than the minimum reinforcement requirement.

Maximum spacing of tension bars (slab thickness exceeding 200 mm)

The maximum centre to centre bar spacing for crack control, scr,max, is dependent on the maximum allowable crack width, wmax, specified in the slab properties (with a default value of 0.30 mm).

The service stress in the reinforcement, σs, is given by:

σs = (As,reqd / As,prov) · (fyk / γS) · RPL

where

  • As,reqd = area of reinforcement required for the maximum design Ultimate Limit State moment, MEd
  • As,prov = area of reinforcement provided
  • RPL = permanent load ratio

In the slab properties you are required to supply a value for the permanent load ratio, RPL. A default of 0.65 has been assumed, but you are advised to consider if this is appropriate and adjust as necessary.

The maximum allowable centre to centre bar spacing, scr,max, is then obtained from table 7.3N (shown below) by looking up the calculated value of the service stress in the reinforcement, σs, using interpolation between values of σs.

Steel service stress, σs (N/mm2)

Maximum allowable bar spacing for crack control, scr,max
wmax = 0.40 mm wmax = 0.30 mm wmax = 0.20 mm
≤ 160 300 300 200
200 300 250 150
240 250 200 100
280 200 150 50
320 150 100 Warning
360 100 50 Warning
> 360 Warning Warning Warning

Minimum area of reinforcement

The minimum area of longitudinal tension reinforcement, As,min, is given by:2

As,min ≥ max[kmin1 · b · d · (fctm / fyk), kmin2 · b · d]

where

  • kmin1 = the appropriate NDP value
  • kmin2 = the appropriate NDP value
  • fctm = mean value of the axial tensile strength of the concrete
  • fyk = characteristic yield strength of the reinforcement
  • d = effective depth of reinforcement layer under consideration
For design in accordance with:
  • EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA, Norwegian NA, and Swedish NA:

    kmin1 = 0.26

    kmin2 = 0.0013

Note:

There is no requirement to have a minimum area of compression reinforcement.

The minimum area of longitudinal tension reinforcement for crack control, As,min,cr, is given by:3

As,min,cr ≥ 0.4 · k · fctm · Act / σs

where

  • k = 0.65

    (it is assumed that slabs will always be > 800 mm wide)

  • fctm = mean value of axial tensile strength of concrete

    0.30 · fck(2/3) for concrete grades ≤ C50/60

    2.12 · ln(1 + ((fck + 8) / 10)) for concrete grades > C50/60

  • σs = the reinforcement service stress appropriate for the bar spacing of the reinforcement provided
  • Act = area of concrete in tension just before formation of first crack

    = b · y where y = the distance of the Elastic NA from bottom of slab

The minimum area of longitudinal tension reinforcement required, As,min,reqd, is then given by:

As,min,reqd ≥ max(As,min, As,min,cr)

Maximum area of reinforcement

The maximum area of longitudinal tension reinforcement, Ast,max, is given by:4

Ast,max ≤ kmax · Ac

The maximum area of longitudinal compression reinforcement, Asc,max, is given by:

Asc,max ≤ kmax · Ac

where

  • kmax = the appropriate NDP value
  • Ac = the cross sectional area of the slab design section

    = h · b

For design in accordance with:
  • EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Norwegian NA:

    kmax = 0.04

  • Finnish NA, Swedish NA:

    Ast,max = Asc,max = unlimited

Footnotes

1 EN 1992-1-1:2004 Section 8.2(2)
2 EN 1992-1-1:2004 Section 9.2.1.1(1)
3 EN 1992-1-1:2004 Section 7.3.2(2)
4 EN 1992-1-1:2004 Section 9.2.1.1(3)