Design parameters for horizontal bars (concrete wall: ACI 318)

Modified: 9 Nov 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer
Note: For some of the horizontal bar parameters, additional user defined limits can be applied - where this is the case minimum and maximum values can be specified from the Design tab on the ribbon by clicking Settings > Concrete > Wall > Reinforcement Layout.

Minimum and Maximum Reinforcement Area

The code provisions which control the horizontal reinforcement area are:

  • Limiting minimum ratio of horizontal reinforcement area to gross concrete area, rh,lim,min
  • Limiting maximum ratio of horizontal reinforcement area to gross concrete area, rh,lim,max

The controlling values are:

If dbv ≤ No. 5 (No. 16) with fy ≥ 60000 psi (420 MPa) OR WWR ≤ W31 or D31:

then ρh,lim,min = 0.002, else 0.0025 for all other deformed bars

Total minimum area of horizontal reinforcement, As,min = ρh,lim,min · Acg

Total maximum area of vertical reinforcement, As,max = ρh,lim,max · Acg = 0.08 · Acg

where Acg = gross area of the concrete wall

You can select a minimum ratio which will be the start point for the design via the Design Settings as mentioned in the Note above.

Minimum and Maximum Horizontal Bar Spacing

This is identical in principle to min vertical bar spacing.

Minimum and Maximum Confinement Bar Spacing

There are Code provisions that control the maximum spacing:

The recommended values are:

Limiting maximum transverse spacing, sw,lim,max = min(16 · dbv, 48 · dbw, hw)