Member strength checks (ULS) (Composite beams: EC4)

Modified: 16 Oct 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer

It is assumed that there are no loads or support conditions that require the web to be checked for transverse force. (clause 6.5)

Member strength checks are performed at the point of maximum moment, the point of maximum shear, the position of application of each point load, and at all other points of interest along the beam.

Shear capacity (Vertical)

The resistance to vertical shear, VRd, is taken as the resistance of the structural steel section, Vpl,a,Rd. The contribution of the concrete slab is neglected in this calculation.

The shear check is performed in accordance with EC3, 6.2.6.

Moment capacity

For full shear connection the plastic resistance moment is determined in accordance with clause 6.2.1.2. For the partial shear connection clause 6.2.1.3 is adopted, in which the relation between MRd and Nc is determined using the convex curve ABC shown in Figure 6.5.

In these calculations the steel section is idealized to one without a root radius so that the position of the plastic neutral axis of the composite section can be determined correctly as it moves from the flange into the web.

Where the vertical shear force, VEd, exceeds half the shear resistance, VRd, a (1- ρ) factor is applied to reduce the design strength of the web - as per clause 6.2.2.4.

Shear capacity (Longitudinal)

The design condition to be checked is: vEd ≤ vRd where:

vEd = design longitudinal shear stress

vRd = design longitudinal shear strength (resistance)

vEd is evaluated at all relevant locations along the beam and the maximum value adopted.

vRd is evaluated taking account of the deck continuity, its orientation and the provided reinforcement.

This approach uses the “truss analogy” from EC2. (See Figure 6.7 of EC2).

In these calculations, two planes are assumed for an internal beam, and one for an edge beam. Only the concrete above the deck is used in the calculations.

The values of vRd based on the concrete “strut” and the reinforcement “tie” are calculated. The final value of vRd adopted is then taken as the minimum of these two values.

The angle of the strut is minimised to minimise the required amount of reinforcement - this angle must lie between 26.5 and 45 degrees.

In the calculations of vRd the areas used for the reinforcement are as shown in the following table.

Decking angle Reinforcement type Area used
perpendicular transverse that of the single bars defined or for mesh the area of the main wires[1]
other that of the single bars defined or for mesh the area of the main wires[1]
parallel transverse that of the single bars defined or for mesh the area of the main wires[1]
other single bars have no contribution, for mesh the area of the minor wires[2]

[1]These are the bars that are referred to as longitudinal wires in BS 4483: 1998 Table 1.

[2]These are the bars that are referred to as transverse wires in BS 4483: 1998 Table 1.

If the decking spans at some intermediate angle (θr) between these two extremes then the program calculates:

  • the longitudinal shear resistance as if the sheeting were perpendicular, vRd,perp,

  • the longitudinal shear resistance as if the sheeting were parallel, vRd,par,

  • then the modified longitudinal shear resistance is calculated from these using the relationship, vRd,perpsin2(θr) + vRd,parcos2(θr).