Seismic cantilevers (beams seismic: ACI 318)

Modified: 6 Nov 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer

Horizontal cantilever structural members in structures assigned to Seismic Design Category D, E or F are required to be designed to the applicable load combinations plus an isolated minimum net upward force of 0.2 times the dead load.

If a cantilever beam has been marked as a seismic cantilever, then provided the seismic design category = D, E or F the minimum design moment at the restrained end is checked as follows:

Calculate minimum positive design moment:

Mmin+ = 0.2 · Me,dead−

where

  • Mmin+ = minimum positive design bending moment at the restrained end
  • Me,dead− = critical negative bending moment at the restrained end due to dead loads only obtained for the considered seismic combination

Check the minimum design moment at the restrained end:

Mu+ ≥ Mmin+

where

  • Mu+ = critical positive design bending moment at the restrained end obtained for the considered seismic combination

If the check fails, the region is designed for Mu+ = Mmin+.