Creating wind loadcases to EC1991 1-4

Modified: 7 Feb 2022 Tekla Structural Designer 2024
2024
Tekla Structural Designer

It is not practical to automatically determine critical combinations and thus required wind loadcases, therefore you control the generation of appropriate Wind Loadcases manually. This is achieved via the Wind Loadcases dialog box (accessed from the Load tab).

The Auto button on the dialog creates a default set of loadcases in each of the directions, i.e.

  • -0.3 for Cpi with -ve roof Cpe; not Overall

  • -0.3 for Cpi with +ve roof Cpe; not Overall

  • +0.2 for Cpi with -ve roof Cpe; not Overall

  • +0.2 for Cpi with +ve roof Cpe; not Overall

  • Overall with zero for Cpi; -ve roof Cpe

Alternatively you can create loadcases manually using the Add button. You then specify which direction the loadcase will be created for and set default values for all the zone loads generated in the loadcase.

Once generated these loadcases are standard loadcases so you can include them in combinations in the normal manner.

Try to use engineering judgement to identify the critical loadcases so that the number of load combinations that need to be considered can be minimized. Use the Delete button to remove wind loadcases you do not wish to consider.

Add loadcases

Note: The following instructions assume that the Structural Factor - Automatically calculate separate cs and cd factors checkbox at the bottom of the dialog is unchecked. This checkbox can only ever be checked if working to the UK National Annex.
  1. Click Add to create a row in which to define the loadcase.
  2. Select the Direction the loadcase will be created for.
    The loadcase Name is automatically updated to reflect the input parameters, but it can be edited if required, (by unchecking the Auto checkbox).
  3. Select Overall if the loadcase is to be specifically used for examining the overall behaviour of the structure.
    Note:

    It may be necessary for you to create a second copy of the loadcase with this checkbox cleared if the loadcase is also used for designing elements.

  4. If required, select Use +ve Cpe

    Where 2 sets of coefficients are given in a table for roof zones, this checkbox indicates if the negative or positive Cpe value is to be used.

  5. Specify the required value of the internal pressure coefficient, Cpi
  6. Specify the required value of the structural factor, cscd
  7. Click OK to finish, or Add to continue adding more loadcases.

Auto generate loadcases

Note: The following instructions assume that the Structural Factor - Automatically calculate separate cs and cd factors checkbox at the bottom of the dialog is unchecked. This checkbox can only ever be checked if working to the UK National Annex.
  1. Click Auto.
    5 loadcases are automatically generated in each of the four directions.
  2. Check the loadcases are as you require.
  3. Specify the required value of the structural factor, cscd for each case.
  4. Click OK to finish.

Add loadcases using size and dynamic factors (UK National Annex only)

The UK National Annex states that the Structural Factor, cscd may be separated into a size factor cs and a dynamic factor cd.

  1. Ensure the Structural Factor - Automatically calculate separate cs and cd factors checkbox is selected.
    Note: When the above checkbox is selected cd is calculated using Figure NA.9, taking into account the Structural Damping, δs value (default 0.050) specified by the user. cs is calculated using Table NA.3.
  2. Specify the required Structural Damping, δs value.
  3. Click Add to create a row in which to define the loadcase.
  4. Select the Direction the loadcase will be created for.
    The loadcase Name is automatically updated to reflect the input parameters, but it can be edited if required, (by unchecking the Auto checkbox).
  5. Select Overall if the loadcase is to be specifically used for examining the overall behaviour of the structure.
    Note:

    It may be necessary for you to create a second copy of the loadcase with this checkbox cleared if the loadcase is also used for designing elements.

    When Overall is selected the b+h cell is marked inactive. In this case, for each wall and roof, the program calculates b+h using b & h from the zone properties for the relevant wind direction.

  6. If Overall is not selected, specify b+h

    When designing elements, (beams, columns, braces etc), Table NA.3 in the UK NA implies that b and h should be the width and height respectively of an element. Due to the nature of the loads in the program, it is not practical to do this automatically, and so you should specify a value to be used in the loads generated for this loadcase (default 5.0m).

  7. If required, select Use +ve Cpe

    Where 2 sets of coefficients are given in a table for roof zones, this checkbox indicates if the negative or positive Cpe value is to be used.

  8. Specify the required value of the internal pressure coefficient, Cpi
    To be calculated by you from Clause 7.2.9.
  9. Click OK to finish, or Add to continue adding more loadcases.

Auto generate loadcases using size and dynamic factors (UK National Annex only)

The UK National Annex states that the Structural Factor, cscd may be separated into a size factor cs and a dynamic factor cd.

  1. Ensure the Structural Factor - Automatically calculate separate cs and cd factors checkbox is selected.
    Note: When the above checkbox is selected cd is calculated using Figure NA.9, taking into account the Structural Damping, δs value (default 0.050) specified by the user. cs is calculated using Table NA.3.
  2. Specify the required Structural Damping, δs value.
  3. Click Auto.
    5 loadcases are automatically generated in each of the four directions.
  4. Check the loadcases are as you require, then click OK to finish.

Review wind loadcases

Once wind loadcases have been created they can be reviewed graphically by opening a wind view for the required direction and then selecting the desired wind loadcase from the Loading list.