Why is a reduction factor (RF) applied to all columns in Tekla Structural Designer and not the Tekla Tedds "RC column design to EC1992" calculation?

Tekla Structural Designer - Not version-specific Concrete Design Reduction Factor RF 10% reduction Cl 3.1.7(3) Compression Zone
Not version-specific
Tekla Structural Designer
Environment
Eurocode

Question

Why is a reduction factor (RF) applied to all columns in Tekla Structural Designer and not the Tekla Tedds "RC column design to EC1992" calculation?

 
Image
image.png

Answer

Tekla Tedds uses a different and more approximate biaxial bending check method to that of Tekla Structural Designer, meaning that a 10% reduction of the concrete strength is not applied in the Tedds software for rectangular sections.
 
Note that the 10% reduction (displayed in Tekla Structural Designer results as a reduction factor RF = 0.9, see screenshot above) comes from the following Clause and rationale:
 
EC2 section 3.1.7(3):

“Note: If the width of the compression zone decreases in the direction of the extreme compression fibre, the value ηfcd should be reduced by 10%”

This is always applied, the rationale being as follows:

It was decided to always use this reduction for rectangular sections; the general case is biaxial bending and so the axial-moment interaction check is most commonly carried out at some non-zero resultant.  Hence, this is conservative only in situations where the concrete area doesn’t reduce – which should generally be rare.  Therefore, the reduction should also be applied in the ultimate axial resistance check – which means that the ultimate axial resistance matches the peak position of the interaction diagram.