Slenderness ratio
The slenderness ratio, λ, of the restrained length about each axis is calculated as follows:
λ = l0 / i = l0 / √(I / A)
where
- l0 is the effective height of the stack
- i is the radius of gyration of the stack section about the axis under consideration
- I is the second moment of area of the stack section about the axis
- A is the cross-sectional area of the stack section
The slenderness ratio λ is then checked against the limiting slenderness ratio λlim in each direction. If the slenderness is less than this limit, then the member is short and slenderness effects are ignored; otherwise it is slender.
Limiting slenderness ratio
λlim = 20 · A · B · C / √n
where
- A = 1 / (1 + (0.2 · φef)) ≥ 0.7
- B = √(1 + (2 · ω)) ≥ 1.1
- C = 1.7 − rm
where
- φef is the effective creep ratio
- ω = As · fyd / (Ac · fcd)
- fyd is the design yield strength of the reinforcement
- fcd is the design compressive strength of the concrete
- As is the total area of longitudinal reinforcement
- n = NEd / (Ac · fcd)
- NEd is the design axial force between restrained floor levels in this direction
- rm = M1.1 / M2.1
- M1.1 and M2.1 are the first order moments at the ends of the stack about the axis being considered, with |M2.1| ≥ |M1.1|
If M1.1 and M2.1 cause tension in the same side of the stack then rm is positive and C ≤ 1.7. If the converse is true then the stack is in double curvature, and it follows that rm is negative and C > 1.7.
For braced stacks in which the first order moments arise only from transverse loads (lateral loading is significant) or imperfections (Mimp.1 > |M2.1|), C must be taken as 0.7.
For bracing stacks, C must be taken as 0.7.
For restrained lengths encompassing more than one stack, C is taken as 0.7.
The effective creep ratio, φef, is derived as follows:
fcm = fck + 8 N/mm2
h0 = 2 · Ag / u
where
- u is the section perimeter in contact with the atmosphere (assumed to be the full section perimeter)
- Ag is the gross section area
α1 = (35 / fcm)0.7
α2 = (35 / fcm)0.2
α3 = (35 / fcm)0.5
If fcm ≤ 35 N/mm2:
βH = (1.5 · (1 + (1.2 · RH))18 · h0) + 250 ≤ 1500
else:
βH = (1.5 · (1 + (1.2 · RH))18 · h0) + (250 · α3) ≤ 1500 · α3
where RH is the relative humidity, which is set under Design parameters in the column properties
βc(t, t0) = ((t − t0) / (βH + t − t0))0.3
βt0 = 1 / (0.1 + t00.2)
βfcm = 16.8 / √fcm
where t0 is the age of column loading and defaults to 14 days; if required it can be changed under Design parameters in the column properties
If fcm ≤ 35 N/mm2:
φRH = 1 + ((1 − (RH / 100)) / (0.1 · h01/3))
else:
φRH = (1 + (((1 − (RH / 100)) / (0.1 · h01/3)) · α1)) · α2
then:
φ0 = φRH · βfcm · βt0
φ(∞, t0) = φ0 · βc(∞, t0)
If φ(∞, t0) ≤ 2 and λ < 75 and Mmax.1 / NEd ≥ h and ω ≥ 0.25:
φef = 0
else:
φef = φ(∞, t0) · RPL
where
- Mmax.1 is the largest first order moment in the restrained length in this direction
- NEd is the design axial force in the restrained length in this direction
- RPL is the permanent load ratio
You are required to supply a value for the permanent load ratio which is located under Design parameters in the column properties. A default of 0.65 has been assumed, but you are advised to consider if this is appropriate and adjust as necessary.
Tekla Structural Designer assumes that t∞ (t-infinity) is equal to 70 years (25550 days).
Pre-selection of Bracing Contribution
The significant parameter within the slenderness criteria is a choice of how a wall, or column, is contributing to the stability of the structure.
In-plane direction, a wall is usually considered to be a bracing member. Out-of-plane direction, a wall is usually considered to be braced by other stabilizing members. These are the default settings but can be edited.