Slender span (concrete beam: EC2)

Modified: 6 Nov 2026 Tekla Structural Designer 2025
2025
Tekla Structural Designer

Slender span check

Second order effects associated with lateral instability may be ignored if beams are within the geometric limits given by the following:

L0t ≤ 50 · bcomp / (h / bcomp)1/3 and h / bcomp ≤ 2.5

where

  • L0t = distance between torsional restraints, taken in Tekla Structural Designer as the distance between faces of supports
  • h = total overall depth of the beam at the center of L0t
  • bcomp = width of the compression flange of the beam (= bw for rectangular sections and beff for flanged beams)

If either of the above checks fail then a Warning is displayed.

Ignore lateral instability

This option (located In the beam properties under the Analysis & design control heading) allows you to consider or ignore lateral instability for slender spans to Eurocode 2 Clause 5.9(1). When the option is checked on the slender span check is excluded from design.